Building water supply and drainage fire pump choice

Temporary high-pressure fire water supply system fire pump should be used in a prepared, or a multi-purpose spare, standby fire pump working capacity should not be less than one of the largest working fire pump. When a multi-purpose equipment, should consider more than one fire pump in parallel, the flow superposition of fire pump outlet pressure. The choice of fire pump, the pump performance curve should be smooth without hump, fire pump zero flow pressure should not exceed 140% of the system design rated pressure, when the pump flow rate of 150% of rated flow, then the fire pump pressure is not Should be less than 65% of rated pressure. Fire pump motor shaft power pump flow should meet the head of the curve at any point on the job requirements.